规格书 |

|
operating travel |
2.6 mm (NO changing electrical state)4.3 mm (total travel) |
product weight |
0.026 kg |
[Ie] rated operational current |
3 A at 240 V, AC-15, A300 conforming to EN/IEC 60947-5-16 A at 120 V, AC-15, A300 conforming to EN/IEC 60947-5-10.1 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-10.22 A at 125 V, DC-13, R300 conforming to EN/IEC 60947-5-1 |
contacts material |
Silver alloy (Ag/Ni) |
[Ith] conventional free air thermal current |
10 A conforming to EN/IEC 60947-5-1 |
device short name |
ZB5 |
product or component type |
Complete body/contact assembly |
contact block type |
Single |
CAD overall height |
42 mm |
contacts type and composition |
2 NO |
contacts operation |
Slow-break |
range of product |
Harmony XB5 |
CAD overall width |
30 mm |
mechanical durability |
5000000 cycles |
contacts usage |
Standard contacts |
connections - terminals |
Plug-in connector |
electrical reliability IEC 60947-5-4 |
Î |
sale per indivisible quantity |
1 |
terminals description ISO n °1 |
(13-14)NO |
[Uimp] rated impulse withstand voltage |
4 kV conforming to EN 60947-1 |
short circuit protection |
4 A cartridge fuse type gG conforming to EN/IEC 60947-5-1 |
CAD overall depth |
32 mm |
fixing collar material |
Plastic |
positive opening |
Without positive opening |
additional information |
With body/fixing collar |
electrical durability |
1000000 cycles, AC-15, 1 A at 230 V, operating rate: 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C1000000 cycles, AC-15, 1.5 A at 120 V, operating rate: 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C1000000 cycles, AC-15, 3 A at 24 V, operating rate: 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C1000000 cycles, DC-13, 0.15 A at 110 V, operating rate: 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C1000000 cycles, DC-13, 0.4 A at 24 V, operating rate: 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C |
[Ui] rated insulation voltage |
250 V (degree of pollution: 3) conforming to EN 60947-1 |