所示图像仅为示意图。请从产品数据表中获得准确的规格。
| Type | Description |
|---|---|
| 工业别名 | 785901202554, LU2B32B |
| 子类别 | Solid State Relay |
| 交货期 | 14 Days |
| product certifications | ABSASEFAATEXBVCCCCSADNVGLGOSTLROS (Lloyds register of shipping)UL |
| vibration resistance | 2 gn 5...300 Hz power poles open conforming to IEC 60068-2-274 gn 5...300 Hz power poles closed conforming to IEC 60068-2-27 |
| operating time | 150 ms with change of direction for power circuit35 ms opening for control circuit70 ms closing for control circuit75 ms without change of direction for power circuit |
| resistance to fast transients | 2 kV class 3 serial link conforming to IEC 61000-4-44 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
| product weight | 1.27 kg |
| [Ie] rated operational current | 21 A at 690 V23 A at 500 V32 A at <= 440 V |
| [Ith] conventional free air thermal current | 32 A |
| resistance to radiated fields | 10 V/m 3 conforming to IEC 61000-4-3 |
| height | 224 mm |
| [Ics] rated service breaking capacity | 10 kA 500 V4 kA 690 V50 kA 230 V50 kA 440 V |
| control circuit voltage limits | 14.5 V 24 V AC drop-out20...26.5 V 24 V AC in operation |
| device short name | LU2B |
| immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |
| resistance to electrostatic discharge | 8 kV level 3 in open air conforming to IEC 61000-4-28 kV level 4 on contact conforming to IEC 61000-4-2 |
| product or component type | Reversing power base |
| operating rate | 60 cyc/mn |
| Duration of inrush phase | 25 ms for AC network 50/60 Hz |
| safety reliability level | 1369863 cycles20000000 cycles |
| connections - terminals | Control circuit: screw clamp terminals 1 cable 0.34...1.5 mm ² - cable stiffness: flexible - with cable endControl circuit: screw clamp terminals 1 cable 0.75...1.5 mm ² - cable stiffness: flexible - without cable endControl circuit: screw clamp terminals 1 cable 0.75...1.5 mm ² - cable stiffness: rigid - without cable endControl circuit: screw clamp terminals 2 cable 0.34...1.5 mm ² - cable stiffness: flexible - with cable endControl circuit: screw clamp terminals 2 cable 0.75...1.5 mm ² - cable stiffness: flexible - without cable endControl circuit: screw clamp terminals 2 cable 0.75...1.5 mm ² - cable stiffness: rigid - without cable endPower circuit: screw clamp terminals 1 cable 1...10 mm ² - cable stiffness: rigid - without cable endPower circuit: screw clamp terminals 1 cable 1...6 mm ² - cable stiffness: flexible - with cable endPower circuit: screw clamp terminals 1 cable 2.5...10 mm ² - cable stiffness: flexible - without cable endPower circuit: screw clamp terminals 2 cable 1...6 mm ² - cable stiffness: flexible - with cable endPower circuit: screw clamp terminals 2 cable 1...6 mm ² - cable stiffness: rigid - without cable endPower circuit: screw clamp terminals 2 cable 1.5...6 mm ² - cable stiffness: flexible - without cable end |
| typical current consumption | 220 mA at 24 V AC I maximum while closing90 mA at 24 V AC I rms sealed |
| poles description | 3P |
| suitability for isolation | Yes |
| heat dissipation | 3 W for control circuit with LUCA, LUCB, LUCC, LUCD1.8 W for control circuit with LUCM |
| safe separation of circuit | 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N |
| protective treatment | TH conforming to IEC 60068 |
| auxiliary contact composition | 2 NO |
| immunity to voltage dips | 70 % 500 ms conforming to IEC 61000-4-11 |
| ambient air temperature for operation | -25...60 °C with LUCM-25...70 °C with LUCA, LUCB, LUCC, LUCD |
| mechanical durability | 15000000 cycles |
| utilisation category | AC-41AC-43AC-44 |
| shock resistance | 10 gn power poles open conforming to IEC 60068-2-2715 gn power poles closed conforming to IEC 60068-2-27 |
| network frequency | 40...60 Hz |
| IP degree of protection | IP20 front panel and wired terminals conforming to IEC 60947-1IP20 other faces conforming to IEC 60947-1IP40 front panel outside connection zone conforming to IEC 60947-1 |
| control circuit voltage | 24 V AC 50/60 Hz |
| tightening torque | Control circuit: 0.8...1.2 N.m - with screwdriver 5 mm flatControl circuit: 0.8...1.2 N.m - with screwdriver 5 mm Philips no 1Power circuit: 1.9...2.5 N.m - with screwdriver 6 mm flatPower circuit: 1.9...2.5 N.m - with screwdriver 6 mm Philips No 2 |
| fire resistance | 650 °C conforming to IEC 60695-2-12960 °C parts supporting live components conforming to IEC 60695-2-12 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-6-2 |
| immunity to microbreaks | 3 ms |
| [Ue] rated operational voltage | 230 V440 V500 V690 V |
| non-dissipating shock wave | 1 kV serial mode conforming to IEC 60947-6-22 kV common mode conforming to IEC 60947-6-2 |
| standards | CSA C22-2 No 14 type EEN 60947-6-2IEC 60947-6-2UL 508 type E with phase barrier |
| [Ui] rated insulation voltage | 600 V conforming to CSA C22-2 No 14600 V conforming to UL 508690 V conforming to IEC 60947-1 3 |
| depth | 126 mm |
| ambient air temperature for storage | -40...85 °C |
| range of product | TeSys U |
| auxiliary contacts type | Type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1Type mirror contact (1 NC) state of the power conforming to draft IEC 60947-1 |
| operating altitude | 2000 m |
| width | 45 mm |